Wipcool MRM75os Refrigerant Recovery Machine with Oil Separator
Refrigerant recovery machine with a built-in oil separator and an oil-free twin-piston compressor, for group III–V refrigerants including R32, R1234yf (A2L class) and R410A. Liquid recovery of group V refrigerants up to 3.9 kg/min.
- Built-in oil separator
- Twin-piston compressor
- Digital pressure display
- A2L refrigerants, including R32
- 24-month warranty
- Warranty service in Poland
- Service by the distributor in the country of purchase
The MRM75os is a version of the MRM75 recovery machine with a built-in oil separator. It has an oil-free, air-cooled reciprocating compressor with two pistons and a 970 W motor. The machine recovers group III, IV and V refrigerants, including R32 and R1234yf (A2L class) as well as R410A.
You can recover refrigerant as vapour, as liquid or using the Push/Pull method, and you select the mode with a knob. The digital display and control keys are on top of the housing. Once recovery is complete, the machine purges itself with the knob in the PURGE position.
In the box
- MRM75os refrigerant recovery machine
- Power cordLength 1.8 m
- Filter
- Shoulder strap
- Charging hose
- User manual
Technical specifications
| Power supply | 230 V |
| Motor power | 970 W |
| Motor speed | 3000 obr./min |
| Max. current | 6,5 A |
| Compressor | Bezolejowa, chłodzona powietrzem, tłokowa |
| Automatic shut-off | 38,5 bar |
| Operating temperature | 0–40 °C |
| Dimensions (L × W × H, mm) | 386 × 255 × 276 |
| Net weight | 11,6 kg |
| Oil separator | With separator |
| Units per carton | 1 pc |
| Group III refrigerants | R134a, R401C, R406A, R500, R1234yf |
| Group IV refrigerants | R401A, R401B, R402B, R407C, R407D, R408A, R409A, R411A, R411B, R412A, R502, R509 |
| Group V refrigerants | R402A, R404A, R407A, R407B, R410A, R507, R32 |
| Vapour recovery (groups III / IV / V) | 0.5 / 0.7 / 0.7 kg/min |
| Liquid recovery (groups III / IV / V) | 2.6 / 3.0 / 3.9 kg/min |
| Push/Pull (groups III / IV / V) | 8.2 / 9.3 / 10.5 kg/min |
Features and equipment
This equipment must only be operated by qualified personnel. Read the user manual before first use.