WipcoolDistribution PL · 4REF

Wipcool PT-25 user manual

Waterless Condensate Trap

Read the entire manual before first use. Keep it for as long as you use the device.

Wipcool PT-25 Waterless Ball Condensate Trap
1

Wipcool PT-25 user manual

The Wipcool PT-25 waterless condensate trap is used to drain condensate from air conditioning systems. A floating ball limits the entry of outside air, odours and insects through the drain pipe.

The user manual is an integral part of the product. Please read this manual carefully and follow all instructions strictly.

2

General information

Wipcool products are designed for professional use by qualified air conditioning and refrigeration engineers. As the manufacturer, Wipcool specifies that our products should only be operated by suitably qualified and trained persons.

  • ■Observe all local safety regulations and general safety standards when using the Wipcool PT-25 waterless condensate trap.
  • ■Keep the user manual near the product so that personnel can access it easily at all times.
  • ■Before use, qualified personnel should read the user manual carefully and understand all the instructions it contains.
  • ■The manufacturer accepts no liability for any damage resulting from improper use, failure to follow the user manual, lack of personnel qualifications or any unauthorised modifications to the product.
  • ■The general terms and conditions of sale contained in the sales documents apply.
3

Symbols and conventions

  1. 01Notice - risk of product damage or an incorrect result.
4

Safety information

  • ■Only a qualified installer may carry out installation and maintenance.
  • ■Before installation and use, check the condensate trap for damage.
  • ■The condensate trap is made of plastic. Do not use it at high temperatures or near sources of heat or fire.
!
Caution
Do not connect the condensate trap to a drain carrying liquid above 40 °C.
!
Caution
The condensate trap limits water backflow but does not stop it completely.
5

Technical specifications

ParameterValue
ModelPT-25
Internal diameterØ25 mm
External diameterØ32 mm
Negative pressure1200 Pa (0.012 bar)
Maximum liquid temperature40 °C
Dimensions (L × W × H)150 × 49.6 × 70 mm
6

Construction

Figure 1. Construction of the PT-25 condensate trap: cover, floating ball, inner housing and body.
Figure 1. Construction of the PT-25 condensate trap: cover, floating ball, inner housing and body.

Dimensions

Figure 2. Condensate trap dimensions in mm.
Figure 2. Condensate trap dimensions in mm.
7

Contents

  • ■PT-25 waterless condensate trap.
  • ■User manual.

After unpacking, check that the contents are complete and in good condition. Report any missing items or transport damage to the seller.

8

Transport and storage

  • ■Transport the condensate trap in its original packaging. Protect the condensate trap from impacts.
  • ■Store the condensate trap in a dry place, away from direct sunlight and sources of heat and fire, at a temperature of -20 to +60 °C.
9

Application

The condensate trap is used in condensate drains from air handling units, ceiling-mounted air conditioning units and cold rooms. It can be used in negative-pressure rooms in hospitals, as well as in laboratories, schools, hotels and food processing facilities.

10

Installation

  1. 01Provide an access opening near the condensate trap installation site to allow inspection and cleaning.
  2. 02Position the condensate trap horizontally. Support the pipes close to the condensate trap body.
  3. 03Close the cover completely.
Figure 3. Installation examples: without a condensate pump on the left, with a condensate pump on the right.
Figure 3. Installation examples: without a condensate pump on the left, with a condensate pump on the right.
11

Use

Inspection after installation and reconnection of the pipes

  1. 01Run water into the drain and observe the flow. Check that the water drains without backing up or pooling and that the cover and connections are watertight.
  2. 02If water backs up, pools or leaks, stop the water supply. Check that the condensate trap is horizontal, the cover is closed and the pipe connections are secure.
  3. 03After correcting any faults, repeat the flow and leak checks.
12

Maintenance

!
Caution
Do not use acetone, thinners, alcohol, petrol, solvents, corrosive substances or strong detergents.

Inspection and cleaning

!
Caution
Do not exert force on the pipes when opening or closing the cover.
  1. 01Open the cover and remove the inner housing and floating ball.
  2. 02Remove dirt and blockages. Clean the removed parts with clean water and a small amount of mild soap, then rinse them thoroughly.
  3. 03Reinstall the cleaned inner housing and floating ball.
  4. 04Close the cover completely and check for water leaks.
  5. 05Check the pipe connections to the body. After reconnecting the pipes, carry out the inspection described in the ‘USE’ section.
13

Service and documents

Before submitting a service request, have the following ready:

  • ■Model - shown on the product label and on the invoice.
  • ■Serial number - if there is no serial number, provide the production number (e.g. 11/2025), usually found on the underside of the product.
  • ■Proof of purchase - an invoice or receipt from an authorised distributor.
  • ■Description of the fault - what is happening, when it started and under what conditions.

You can submit a service request at wipcool.pl/serwis. You will also find the warranty terms there.

4REF sp. z o.o. · ul. Andersa 38, 15-113 Białystok · bok [at] wipcool.plPT-25 · vWydanie 31.10.2026